DMS 4.2 EN 07/2011 TD17

L

51

Control technology | CANopen communication manual

Commissioning the CANopen Logic bus

Commissioning of field devices

8.3.5

Commissioning of I/O system 1000 (EPM-Sxxx)

The I/O system can be parameterised in two ways:

Parameter setting with the »Engineer«

1. Start the »Engineer«.
2. Open or create an »Engineer« project.
3. Insert the I/O system as component.
4. Go online with the I/O system via the CANopen bus.
5. Parameterise the I/O system.
6. Save the parameter set with mains failure protection via CANopen Index 1010.

Parameter setting from the control
In this case you can implement the I/O system immediately into the PLC program and enter

the required values into the Control Configuration under the Service Data Objects tab.

Note!

CAN settings must be made in the »PLC Designer« since the settings are

transferred from the control to the I/O system.