Commissioning the CANopen Logic bus

Commissioning of field devices

50

L

DMS 4.2 EN 07/2011 TD17

8.3.4

Commissioning of I/O system IP20 (EPM-Txxx)

The I/O system can be parameterised in three ways:

Parameter setting with the »Engineer«

1. Start the »Engineer«.
2. Open or create an »Engineer« project.
3. Insert the I/O system as component.
4. Go online with the I/O system via the CANopen bus.
5. Parameterise the I/O system.
6. Save the parameter set with mains failure protection via C16380.

Parameter setting with the »Global Drive Control«

1. Start the »GDC«.
2. Start the search for controllers at the CANopen bus and select the found I/O

system.
Or first select the I/O system offline and then go online.

3. Parameterise the I/O system.
4. Save the parameter set with mains failure protection via CANopen Index 1010.

Parameter setting from the control

 In this case you can implement the I/O system immediately into the PLC program and

enter the required values into the Control Configuration under the Service Data

Objects tab.

 This is appropriate if you only want to change a few parameters compared to the Lenze

default setting and know the values to be set.

Note!

CAN settings must be made in the »PLC Designer« since the settings are

transferred from the control to the I/O system.