Control technology | canopen communication manual – Lenze CANopen control technology User Manual

Page 49

Advertising
background image

DMS 4.2 EN 07/2011 TD17

L

49

Control technology | CANopen communication manual

Commissioning the CANopen Logic bus

Commissioning of field devices

7. Export the EDS file.

• To clearly identify the EDS file in the »PLC Designer« during import, clearly

rename the device before export in the »Engineer«. (you can e.g. manually

precede each device name in the »Engineer« with the project name.)

• The »PLC Designer« only displays the device name contained in the EDS file.
Highlight the CAN interface of the Inverter Drive 8400 to be connected to the

control in the project tree. Then select the "EDS export …" command from the

context menu.

8. Save the file to any folder, logically to your total project directory. You should not

change the suggested file name. The »Engineer« reports that the file has been

created.
You must reimport the EDS file after doing the following in the »Engineer« …
• replacing the application,
• adding, deleting, renaming a port under the Ports tab or changing its

application variables,

• adding, deleting function blocks that can be parameterised in the FB Editor or

changing their code number range.

If you reimport the EDS file, you should overwrite the existing EDS file. It is not

reasonable to create several file versions with the same device name since you

cannot distinguish them in the »PLC Designer«.

Advertising