Control technology | CANopen communication manual

Commissioning the CANopen Logic bus

Commissioning of field devices

7. Connect the signal which are to be communicated with the IPC with ports via the

FB Editor of the »Engineer«. If possible, use the predefined multiplexers and ports

for this purpose.

• If the possible settings of the predefined multiplexers are not sufficient for your

purposes, activate the FB Editor and draw lines.

• Ports are the variables of the application which can be communicated

outwards. In one port, several signals can be combined to a structure. If the

predefined ports are not sufficient for your purposes, you can change the

structure of the ports or define your own ports under the Ports tab. Before this,

you must activate the application in the FB Editor.

• When the function block interconnection is completed and all required ports are

defined, update the project.

• Retransfer the application to the Servo Drive 9400. Execute a "CAN Reset Node"

on the correct interface via C00002. The device now expects its initialisation

through the control. The green CAN-LED at the Servo Drive 9400 or CAN module

is blinking.