Control technology | CANopen communication manual

Commissioning the CANopen Logic bus

Preparing the restart

68

L

DMS 4.2 EN 07/2011 TD17

8.9

Preparing the restart

In the control technology system you can use the control to transmit the entire parameter

setting via SDO initialisation to the field devices when the machine is switched on.
According to DS301, the control always initialises the CAN parameters of the field devices.

Moreover, it can initialise further parameters. The values for this must be stored in the

control configuration under the Service Data Objects tab.
Usually, the control only transmits those SDO projects for which you have stored another

value than the standard value. The control does not compare these values with the existing

values in the field device. Thus, not all parameters changed there may be set correctly.
If you want that a factory adjustment is carried out in the field device before SDO

initialisation, go to the Parameter tab and set a checkmark at "Reset Node".

The Service Data Objects tab contains the codes which are written in the EDS file. The EDS

file contains all write codes.

Note!

When a node is reset, the parameter setting in the field device which you have

made with the »Engineer« or the »Global Drive Control« gets lost. For this reason

you have to transmit all parameter values manually to the Service Data Objects

tab. This only makes sense when commissioning is completed and all

parameters are optimised. If you change something afterwards via the

»Engineer« or the »Global Drive Control«, you have to maintain it in the PLC

program.