M1100 series ratings – Lenze MC1000 Series User Manual
Page 14

10
13435742_EDBM101_v24
5
MC1000 RATINGS
The following tables indicate the input and output ratings of the MC1000 Series.
NOTE: The output current ratings are based on operation at carrier frequencies
of 8 kHz and below. At full ambient temperature, operation at carrier frequencies
above 8 kHz require derating the drive by multiplying the output current rating by
the following factors: 0.94 at 10 kHz, 0.89 at 12 kHz, and 0.83 at 14 kHz. Refer
to Parameter 23 - CARRIER in Section 18 - DESCRIPTION OF PARAMETERS.
NOTE
Refer to Appendix A for derated single phase ratings on selected models.
M1100 SERIES RATINGS
MODEL
INPUT
OUTPUT
(120/240 Vac, 50 - 60 Hz)
(0 - 230 Vac)
MODEL
NUMBER
1
FOR MOTORS
NOMINAL
NOMINAL
RATED
INPUT CURRENT
2
POWER
CURRENT
POWER
HP
kW
PHASE
(AMPS)
(KVA)
(AMPS)
(KVA)
M1103S
0.25
0.18
1
6.0 / 3.0
0.72
1.4 / 1.4
0.56
M1105S
0.5
0.37
1
9.2 / 4.6
1.1
2.2 / 2.2
0.88
M1110S
1
0.75
1
16.2 / 8.1
1.9
4.0 / 4.0
1.6
M1115S
1.5
1.1
1
21 / 10.4
2.5
5.2 / 5.2
2.1
1
Refer to Section 3 for model number breakdown.
2
Refer to Section 8 for recommended fuse type.