MC1000 RATINGS

The following tables indicate the input and output ratings of the MC1000 Series.
NOTE: The output current ratings are based on operation at carrier frequencies

of 8 kHz and below. At full ambient temperature, operation at carrier frequencies

above 8 kHz require derating the drive by multiplying the output current rating by

the following factors: 0.94 at 10 kHz, 0.89 at 12 kHz, and 0.83 at 14 kHz. Refer

to Parameter 23 - CARRIER in Section 18 - DESCRIPTION OF PARAMETERS.

NOTE

Refer to Appendix A for derated single phase ratings on selected models.

M1100 SERIES RATINGS

MODEL

INPUT

OUTPUT

(120/240 Vac, 50 - 60 Hz)

(0 - 230 Vac)

MODEL

NUMBER

1

FOR MOTORS

NOMINAL

NOMINAL

RATED

INPUT CURRENT

2

POWER

CURRENT

POWER

HP

kW

PHASE

(AMPS)

(KVA)

(AMPS)

(KVA)

M1103S

0.25

0.18

1

6.0 / 3.0

0.72

1.4 / 1.4

0.56

M1105S

0.5

0.37

1

9.2 / 4.6

1.1

2.2 / 2.2

0.88

M1110S

1

0.75

1

16.2 / 8.1

1.9

4.0 / 4.0

1.6

M1115S

1.5

1.1

1

21 / 10.4

2.5

5.2 / 5.2

2.1

1

Refer to Section 3 for model number breakdown.

2

Refer to Section 8 for recommended fuse type.