Lenze MC1000 Series User Manual

Page 26

Advertising
background image

22

13435742_EDBM101_v24

11

MC1000 POWER WIRING DIAGRAM

T1

T2 T3

L1 L2

L3

FUSED INPUT

VOLTAGE

GND

GND

GND

DISCONNECT

MEANS

(REQUIRED)

THREE PHASE

AC MOTOR

240 Vac SINGLE

PHASE INPUT

WIRING DIAGRAM

120 Vac SINGLE

PHASE INPUT

WIRING DIAGRAM

L1 L2 N

L1 L2 N

WARNING!

Do not connect incoming AC power to output terminals T1, T2, or T3!

Severe damage to the drive will result.

INSTALL, WIRE, AND GROUND IN ACCORDANCE WITH ALL APPLICABLE

CODES.
NOTES:

1. Wire the motor for the proper voltage per the output rating of the drive. Motor

wires MUST be run in a separate steel conduit away from control wiring and

incoming AC power wiring.

2. Do not install contactors between the drive and the motor. Damage to the

drive may result. Refer to Section 10.1.

3. Remove any existing, and do not install, power factor correction capacitors

between the drive and the motor. Failure to do so will result in drive

damage.

4. Use only UL and CSA listed and approved wire.
5. Minimum wire voltage ratings: 300 V for 120, 200 and 240 Vac systems,

and 600 V for 400, 480, and 590 Vac systems.

6. Wire gauge must be based on a minimum of 125% of the rated input/output

current of the drive, and a minimum 75°C insulation rating. Use copper wire

only.

7. Wire and ground in accordance with NEC or CEC, and all applicable local

codes.

8. Refer to Appendix A for alternate single phase wiring configuration on

selected models.