Parameter menu – Lenze MC1000 Series User Manual

Page 46

Advertising
background image

42

13435742_EDBM101_v24

PARAMETER MENU

PARAM.

NUMBER

PARAMETER

NAME

RANGE OF

ADJUSTMENT

FACTORY

DEFAULT

28

AUTO/MAN

AUTO, MANUAL, BOTH

BOTH

29

MANUAL

KEYPAD, 0-10 VDC

KEYPAD

30

CONTROL

LOCAL, REMOTE, BOTH

LOCAL

31

UNITS

sp: HERTZ, RPM, % HZ,

/SEC, /MIN, /HR, GPH, NONE

pid: %, PSI, FPM, CFM, GPM,

IN, FT, /SEC, /MIN, /HR, F, C,

MPM, GPH

sp: HERTZ

32

HZ MULT

0.10 - 650.0

1.00

33

SPEED DP

XXXXX, XXX.X, XX.XX,

X.XXX, .XXXX

XXXXX

34

LOAD MLT

95 - 139 %

100 %

35

CONTRAST

LOW, MED, HIGH

MED

36

SLEEP TH

0.00 - 360.0 Hz

0.00 Hz

37

SLEEP DL

0.0 - 300.0 SEC

30.0 SEC

38

SLEEP BW

FB @ MIN - FB @ MAX

0 %

39

TB5 MIN

0.00 - 360.0 Hz (NOTE 2)

0.00 Hz

40

TB5 MAX

0.00 - 360.0 Hz (NOTE 2)

60.00 Hz

41

AIN FLTR

0.01 - 10.0 SEC

0.02 SEC

42

TB10A OUT

NONE, 0-10V, 2-10V

NONE

43

@TB10A

0.00 - 360.0 Hz

60.00 Hz

44

TB10B OUT

NONE, 0-10V, 2-10V

NONE

45

@TB10B

10 - 200 %

125 %

47

TB13A

NONE, 0-10VDC, 4-20MA,

SPEED#1, LOC SEL,

DEC FREQ

NONE

48

TB13B

NONE, 0-10VDC, 4-20MA,

SPEED#2, INC FREQ,

JOG FWD, JOG REV

NONE

49

TB13C

NONE, 0-10VDC, 4-20MA,

SPEED#3, LOC SEL,

RUN REV, STRT REV

NONE

50

TB13D

EXT FAULT EXT/FAULT,

EXT CLEAR

EXT FAULT

NOTE 2:

MAX LIMIT IS 650 Hz ON UNITS WITH HIGH FREQUENCY SOFTWARE.