Preset activation – Lenze MC1000 Series User Manual

Page 49

Advertising
background image

13435742_EDBM101_v24

45

PRESET ACTIVATION

PRESET #

TB - 13A

TB - 13B

TB - 13C

1

CLOSED

OPEN

OPEN

2

OPEN

CLOSED

OPEN

3

OPEN

OPEN

CLOSED

CLOSED

CLOSED

OPEN

4

CLOSED

OPEN

CLOSED

OPEN

CLOSED

CLOSED

NOTE:

SPEED #4 is selected if any two of the three TB-13 terminals are closed

to TB-2.

5,6

SKIP #1 & #2

(SKIP SPEED #1 & #2)

7

BAND WID

(SKIP BANDWIDTH)

These parameters are used to prevent the drive from operating continuously at critical

speeds, or frequencies, that cause excessive mechanical vibration of the driven

equipment. The SKIP SPEEDS (Parameters 5 and 6) and the SKIP BANDWIDTH

(Parameter 7) are used to define up to two speed avoidance ranges. The SKIP

SPEED settings define the starting point of the speed range that is to be avoided,

and the SKIP BANDWIDTH setting defines how far the speed range extends beyond

SKIP SPEED. Setting the SKIP SPEEDS to .00 Hz disables this function.
Example: The critical frequency is 21 Hz, and a bandwidth of 2 Hz is desired.

Therefore, set SKIP #1 to 20 Hz and set SKIP BANDWIDTH to 2 Hz. This results in

a speed range from 20 Hz to 22 Hz that the drive will not operate within continuously.

If the drive were operating at 25 Hz and then commanded to operate at a speed

within the range of avoidance, the drive would decelerate to 22 Hz and remain at

that frequency until commanded to 20 Hz or below. The drive would then decelerate

through the range of avoidance to the new frequency. Likewise, if the drive were

operating at 18 Hz, and then commanded to operate at a speed within the range of

avoidance, the drive would accelerate to 20 Hz and remain at that frequency until

commanded to a speed of 22 Hz or above. The drive would then accelerate through

the range of avoidance to the new frequency.