MIN/MAX ALARM

The relay energizes when the feedback signal (in PID mode) or

the speed reference signal (in open-loop speed mode) is within

the limits set by MIN ALARM and MAX ALARM (Parameters

81 and 82), and de-energizes when the signal falls below the

MIN ALARM setting or exceeds the MAX ALARM setting.

INV MIN/MAX A

INVERSE MIN/MAX ALARM - The relay de-energizes when the

feedback signal (in PID mode) or the speed reference signal (in

open-loop speed mode) is within the limits set by MIN ALARM

and MAX ALARM (Parameters 81 and 82), and energizes when

the signal falls below the MIN ALARM setting or exceeds the

MAX ALARM setting.

MIN ALARM

The relay de-energizes when the feedback signal (in PID mode)

or the speed reference signal (in open-loop speed mode)

equals or exceeds the MIN ALARM setting (Parameter 81),

and energizes when the signal falls below the MIN ALARM

setting.

INV MIN ALARM

INVERSE MIN ALARM - The relay energizes when the feedback

signal (in PID mode) or the speed reference signal (in open-

loop speed mode) equals or exceeds the MIN ALARM setting

(Parameter 81), and de-energizes when the signal falls below

the MIN ALARM setting.

MAX ALARM

The relay de-energizes when the feedback signal (in PID mode)

or the speed reference signal (in open-loop speed mode) is less

than or equal to the MAX ALARM setting (Parameter 82), and

energizes when the signal exceeds the MAX ALARM setting.

INV MAX ALARM

INVERSE MAX ALARM - The relay energizes when the

feedback signal (in PID mode) or the speed reference signal

(in open-loop speed mode) is less than or equal to the MAX

ALARM setting (Parameter 82), and de-energizes when the

signal exceeds the MAX ALARM setting.

SLEEP

The relay energizes when the drive is in SLEEP MODE. Refer

to Parameters 36 - 38.

SPD = 0HZ

The relay energizes when there is no output to the motor, for

any reason, such as: drive is in STOP mode, drive is in RUN

mode but the speed command is 0 Hz, drive is in SLEEP mode,

drive has tripped into a fault, etc.

The open-collector output circuit is a current-sinking type rated at 30 VDC and 40

mA maximum. An external power supply (30 VDC max.) must be used to power

the open-collector outputs. The drive does not have a dedicated power supply for

the open-collector outputs.
53

TB15 OUT

(TB-15 OPEN COLLECTOR OUTPUT)

This parameter sets the open-collector output indication for terminal TB-15. It has

the same functionality as Parameter 52 - TB14 OUT above.
54

RELAY

(RELAY FUNCTION)

The control board has one set of FORM C relay contacts at TB-16, 17, and 18

that can be programmed for the same indications as the open-collector outputs

described in parameter 52.