20

13435742_EDBM101_v24

9

VOLTAGE SELECTION

M1100 Series drives are rated for 240/120 Vac, 50-60 Hz input. The drive will

function with input voltage of 120 Vac (+ 10%, -15%) at 48 to 62 Hz when wired

for 120 Vac input, or with input voltage of 240 Vac (+ 10%, - 15%), at 48 to 62 Hz,

when wired for 240 Vac input.
M1200 Series drives are rated for 240/200 Vac, 50-60 Hz input. The drive will function

with input voltages of 200 to 240 Vac (+ 10%, - 15%), at 48 to 62 Hz.
M1400 Series drives are rated for 480/400 Vac, 50-60 Hz input. The drive will function

with input voltages of 400 to 480 Vac (+ 10%, - 15%), at 48 to 62 Hz.
M1500 Series drives are rated for 590/480 Vac, 50-60 Hz input. The drive will function

with input voltages of 480 to 590 Vac (+ 10%, - 15%), at 48 to 62 Hz.
To select the proper input voltage on 240/200 VAC 40-60 Hp models, 400/480 VAC

75-150 Hp and 480/590 VAC 75-150 Hp models the PL2 plug must be in the correct

position. PL2 is located either at the lower right corner, or upper right corner of the

power board, depending on horsepower. The PL2 plug is used to select the correct

input voltage. Plug PL2 into the top and middle pins to select 240, 480, or 590 VAC

or the middle and bottom pins to select 200, 400, or 480.

NOTE:

In addition to the voltage plug selection, Parameter 0 – LINE VOLTS must also

be programmed for the proper voltage. Refer to Section 18 - DESCRIPTION OF

PARAMETERS.

Voltage Selection Plug (PL2)

MODEL

CODE

1200
1400
1500

200V

400V

480V

240V
480V
590V

240 / 480 / 590 Vac INPUT

MODEL

CODE

1200

1400

1500

200V

400V

480V

240V
480V
590V

200 / 400 / 480 Vac INPUT

PL2

PL2

Advertising