PASSWORD

(PASSWORD NUMBER)

This feature limits access to the programmable parameters for added security. The

correct password must be entered in order to change the parameters.
Pressing the PROG/RUN button on the keypad will activate the PASSWORD

prompt. If the correct password is entered, the PROGRAM MODE is entered and

parameters can be changed.
If the wrong password is entered, the drive will flash ERROR: INCORRECT and

then return to the PASSWORD prompt to allow another attempt at entering the

correct password.
If the ENTER key is pressed while PASSWORD reads 0000, the MONITOR MODE

will be entered (if Parameter 64 - MONITOR, is set to ON), which will allow the

parameters to be viewed (except for PASSWORD), but not changed.
NOTE 1: The factory default value is 0019.
NOTE 2: If PASSWORD is set to 0000, the function is disabled. Pressing the

PROG/RUN key will result in direct entry into the PROGRAM mode without having

to enter a password.
63

SOFTWARE

(SOFTWARE VERSION)

This parameter displays the software code and revision number of the control board

software. This information is useful when contacting the factory for programming

or troubleshooting assistance. This is a “view-only” parameter, and cannot be

changed.
64

MONITOR

(MONITOR MODE)

This parameter is used to enable (ON) or disable (OFF) the MONITOR MODE

function. The functionality is explained below:
ON

Pressing the PROG/RUN key will call up the PASSWORD

prompt. If the ENTER key is pressed while the password value

reads 0000, the MONITOR MODE is entered and parameters

can be viewed (except for PASSWORD), but not changed.

OFF

Pressing the PROG/RUN key will call up the PASSWORD

prompt. If the ENTER key is pressed while the password value

reads 0000 (or any other incorrect value), it will be treated

as in incorrect password and the display will flash ERROR:

INCORRECT, and then return to the PASSWORD prompt to

allow another attempt at entering the correct password.

65

PROGRAM

(PROGRAM FACTORY DEFAULTS)

WARNING!

STOP ( TB-1) and EXTERNAL FAULT ( TB-13D) circuitry may be

disabled if parameters are reset to factory defaults! The drive must

be reprogrammed after a RESET in order to insure proper operation.

F

AILURE TO DO SO MAY RESULT IN DAMAGE TO EQUIPMENT

AND/OR INJURY TO PERSONNEL!