34

13435742_EDBM101_v24

15

MC1000 CONTROL WIRING DIAGRAMS

15.1

MC1000 TERMINAL STRIP

Shown below is the terminal strip on the main control board, along with a brief

description of the function of each terminal. Wiring shown above the terminal strip

indicates internal wiring on the main control board.

FORM C

RELAY

1 2 5A 5B 6 10A

12A

RXA TXB

10B 2

13A 13B 13C 13D 14 15 2

16 17 18

ST

OP

CIR
CUIT C

OMMON

0-10

VDC SPEED REFERENCE INPUT

10
VDC SUPPL

Y FOR SPEED PO

T

0-10 OR 2-10

VDC OUTPUT

: FREQUENC

Y

0-10 OR 2-10

VDC OUTPUT

: L

O

AD

CIR
CUIT C

OMMON

ST

AR

T

TB

-13A FUNC

TION SELEC

T

TB

-13B FUNC

TION SELEC

T

TB

-13C FUNC

TION SELEC

T

TB

-13D FUNC

TION SELEC

T

OPEN-

COLLEC

TOR OUTPUT

OPEN-

COLLEC

TOR OUTPUT

RS

-485 SERIAL

COMMUNIC

ATIONS

CIR
CUIT C

OMMON

4-20 mA SPEED REFERENCE INPUT

The TB-2 terminals are internally tied together

NOTE
The function of terminals TB-10A, TB-10B, TB-13A, TB-13B, TB-13C,

TB-13D, TB-14, TB-15, TB-16, and TB-18 are dependent on the

programming of certain parameters. In most cases, the name of the

parameter matches the number of the terminal, allowing quick and easy

programming of the terminals to suit the application. The exception is

TB-16 and TB-18, which are governed by Parameter 54 - RELAY.

A complete description of operating the drive in the REMOTE mode can be found

in Section 14.2. The following diagrams provide a quick reference to wire the drive

for the most common configurations.