Lenze MC1000 Series User Manual

Page 64

Advertising
background image

60

13435742_EDBM101_v24

47

TB13A

(TB-13A INPUT FUNCTION)

This parameter is used to select the function of terminal TB-13A. Closing TB-13A

to TB-2 activates the TB-13A input function.
The following functions can be selected:
NONE

Disables the TB-13A function.

0-10VDC

Selects 0-10 VDC as the AUTO speed reference input. The

0-10 VDC signal is wired to TB-5A and TB-2.

4-20 MA

Selects 4-20 mA as the AUTO speed reference input. The 4-20

mA signal is wired to TB-5B and TB-2.

SPEED#1

Selects PRESET SPEED #1 as the AUTO speed reference.

LOC SEL

Selects LOCAL mode when Parameter 30 - CONTROL is set

to BOTH. Drive is in REMOTE mode if contact closure is not

made.

DEC FREQ

Decrease frequency set point. Used with the MOP (motor

operated pot) function. Refer to Section 14.2.6 - SPEED

REFERENCE SELECTION.

48

TB13B

(TB-13B INPUT FUNCTION)

WARNING!

When operating in JOG mode, the STOP key WILL NOT stop the

drive. To stop the drive, the contact between TB-13B and TB-2 must

be opened.

This parameter is used to select the function of terminal TB-13B. Closing TB-13B

to TB-2 activates the TB-13B function. The following functions can be selected:
NONE

Disables the TB-13B function.

0-10VDC

Selects 0-10 VDC as the AUTO speed reference input. The

0-10 VDC signal is wired to TB-5A and TB-2.

4-20 MA

Selects 4-20 mA as the AUTO speed reference input. The 4-20

mA signal is wired to TB-5B and TB-2.

SPEED#2

Selects PRESET SPEED #2 as the AUTO speed reference.

INC FREQ

Increase frequency set point. Used with the MOP (motor

operated pot) function. Refer to Section 14.2.6 - SPEED

REFERENCE SELECTION.

JOG FWD

Jog in the forward direction. Active only when drive is STOPPED.

The jog speed is set by Parameter 2 -SPEED#2.

JOG REV

Jog in the reverse direction. Active only when drive is STOPPED.

The jog speed is set by Parameter 2 - SPEED#2.

49

TB13C

(TB-13C INPUT FUNCTION)

WARNING!

If TB-13C is programmed for RUN REVERSE, TB-1 is disabled and

CANNOT be used as a STOP switch! This is true in LOCAL and

REMOTE mode. Incorrect use of TB-1 may result in damage to

equipment and/or injury to personnel!