Lenze MC1000 Series User Manual

Page 53

Advertising
background image

13435742_EDBM101_v24

49

16

CURRENT

(CURRENT LIMIT)

This parameter sets the maximum allowable output current of the drive, which also

determines the torque capability of the motor. For most applications, CURRENT is

left at the maximum setting, which is 150% or 180% (of the drive’s output current

rating), depending on whether the input voltage to the drive is low or high (refer to

Parameter 0 - LINE VOLTS).
The drive will enter current limit when the current draw of the motor exceeds the

current limit setting. To respond to this condition, the drive will enter "frequency

foldback", which commands the drive to decelerate in order to reduce the output

current and regain synchronization with the motor. When the over current condition

passes, the drive will return to normal operation and reaccelerate to the speed set

point. However, if "frequency foldback" cannot correct the condition and the drive

remains in current limit for too long, it will trip into an OVERLOAD fault. If the drive

enters current limit while accelerating, the time required to reach the speed set point

will be longer than the time programmed into ACCEL (Parameter 8).
Regardless of the CURRENT setting, the drive is capable of delivering a maximum

of 150% current for one minute, and 180% current for approximately 30 seconds,

before tripping into an OVERLOAD fault. Refer to Parameter 17 – MOTOR OL.
17

MOTOR OL

(MOTOR OVERLOAD)

The MC1000 Series is UL approved for solid state motor overload protection.

Therefore, a separate thermal overload relay is not required for single motor

applications. The MOTOR OVERLOAD circuit is used to protect the motor from

overheating due to excessive current draw. The trip time for the MOTOR OVERLOAD

setting is based on what is known as an “inverse I

2

t” function. This function allows

the drive to deliver 150% of the rated output current for one minute, and even higher

current levels for shorter periods of time. Once the overload circuit “times out”, the

drive will trip into an OVERLOAD fault.
The MOTOR OVERLOAD should be set to a value which is equal to the ratio (in

percentage) of the motor full load current rating to the drive output current rating.

This will result in an overload capacity of 150% of the MOTOR current rating for one

minute. If this parameter is set to 100%, the motor will be allowed to draw 150%

of the DRIVE output current rating for one minute. This distinction is important in

cases where the motor full load current rating is significantly less than the drive

output current rating, such as applications where the drive is oversized to meet

torque requirements.
Example 1: A 5 Hp, 480 Vac drive is operating a 3 HP motor with a full load current

rating of 4.8 amps. Divide the motor current rating by the drive output current rating:

4.8 / 7.6 = 63%. Entering this value will allow continuous operation at 4.8 amps,

and will also allow the motor to draw 7.2 amps (150% of 4.8 amps) for one minute.

If the setting is left at 100%, the motor could draw 11.4 amps (150% of 7.6 amps)

for one minute before tripping the drive.
The MC Series drive has two options for thermal overload protection. One depends on the

speed of the drive, and the other does not. The diagram below illustrates the difference

between “speed compensated” and “non-compensated” thermal overload protection.
The “speed-compensated” thermal overload circuit offers additional protection

from high load conditions at low speeds, where motor cooling is often less effective

(e.g., motors with shaft-mounted fans). As seen on the diagram below, the drive

reduces the allowable continuous output current when operating at frequencies

less than 30 Hz.

Advertising