M1400 SERIES RATINGS

MODEL

INPUT

OUTPUT

(400/480 Vac, 50 - 60 Hz)

(0 - 400/460 Vac)

MODEL

NUMBER

1

FOR MOTORS

NOMINAL

NOMINAL

RATED

INPUT CURRENT

2

POWER

CURRENT

POWER

HP

kW

PHASE

(AMPS)

(KVA)

(AMPS)

(KVA)

M1410

1

0.75

3

2.8 / 2.4

2.0

2.3 / 2.0

1.6

M1420

2

1.5

3

4.7 / 4.1

3.4

3.9 / 3.4

2.7

M1430

3

2.2

3

6.6 / 5.7

4.7

5.5 / 4.8

3.8

M1450

5

3.7

3

10.2 / 8.9

7.3

8.7 / 7.6

6.1

M1475

7.5

5.5

3

14.7 / 12.8

10.6

12.6 / 11.0

8.8

M14100

10

7.5

3

18.3 / 15.9

13.2

16.0 / 14.0

11.2

M14150

15

11

3

28 / 24

19.8

24 / 21

16.7

M14200

20

15

3

36 / 31

25.3

31 / 27

21.5

M14250

25

18.5

3

44 / 38

31.9

39 / 34

27.1

M14300

30

22

3

52 / 45

37.6

46 / 40

31.9

M14400

40

30

3

68 / 59

49.0

60 / 52

41.4

M14500

50

37.5

3

85 / 74

61.5

75 / 65

51.8

M14600

60

45

3

100 / 87

72.3

88 / 77

61.3

M14750

75

55

3

109 / 91

75.5

110 / 96

76.5

M141000

100

75

3

139 / 116

96.4

143 / 124

98.8

M141250

125

90

3

175 / 146

121.4

179 / 156

124.3

M141500

150

110

3

202 / 168

139.7

207 / 180

143.4

1

Refer to Section 3 for model number breakdown.

2

Refer to Section 8 for recommended fuse type.