M1200 series ratings – Lenze MC1000 Series User Manual

Page 15

Advertising
background image

13435742_EDBM101_v24

11

M1200 SERIES RATINGS

MODEL

INPUT

OUTPUT

(200/240 Vac, 50 - 60 Hz)

(0 - 200/230 Vac)

MODEL

NUMBER

1

FOR MOTORS

NOMINAL

NOMINAL

RATED

INPUT CURRENT

2

POWER

CURRENT

POWER

HP

kW

PHASE

(AMPS)

(KVA)

(AMPS)

(KVA)

M1205S

0.5

0.37

1

5.8 / 5.0

1.2

2.5 / 2.2

0.9

M1205

0.5

0.37

3

3.1 / 2.7

1.1

2.5 / 2.2

0.9

M1210S

1

0.75

1

10.4 / 9.0

2.2

4.6 / 4.0

1.6

M1210

1

0.75

3

5.5 / 4.8

2.0

4.6 / 4.0

1.6

M1215S

1.5

1.1

1

13.3 / 11.6

2.8

6.0 / 5.2

2.1

M1215

1.5

1.1

3

7.1 / 6.2

2.6

6.0 / 5.2

2.1

M1220S

2

1.5

1

17.1 / 14.9

3.6

7.8 / 6.8

2.7

M1220

2

1.5

3

9.3 / 8.1

3.4

7.8 / 6.8

2.7

M1230S

3

2.2

1

24 / 21

5.0

11.0 / 9.6

3.8

M1230

3

2.2

3

13.0 / 11.3

4.7

11.0 / 9.6

3.8

M1250

5

3.7

3

20 / 17.7

7.4

17.5 / 15.2

6.1

M1275

7.5

5.5

3

30 / 26

10.6

25 / 22

8.8

M12100

10

7.5

3

37 / 32

13.2

32 / 28

11.2

M12150

15

11

3

55 / 48

19.8

48 / 42

16.7

M12200

20

15

3

70 / 61

25.3

62 / 54

21.5

M12250

25

18.5

3

89 / 77

32.0

78 / 68

27.1

M12300

30

22

3

104 / 90

37.6

92 / 80

31.9

M12400

3

40

30

3

119 / 99

41.0

120 / 104

41.4

M12600

3

60

45

3

174 / 145

60.5

177 / 154

61.3

1

Refer to Section 3 for model number breakdown.

2

Refer to Section 8 for recommended fuse type.

3

For branch circuit protection, the 40HP and 60HP 230V models must only be

installed with the appropriately rated UL Listed fuses.

Advertising