ACCEL

(ACCELERATION TIME)

ACCEL sets the acceleration rate for all speed reference sources (keypad, speed

pot, 4-20 mA, 0-10 VDC, jog, and the preset speeds). The ACCEL setting is the time

to accelerate from 0 Hz to the BASE FREQUENCY (Parameter 18). The range of

adjustment for ACCEL depends on horsepower. Refer to the following table:

ACCELERATION LIMITS

120 - 240 Vac

Models

400 - 590 Vac

Models

RANGE OF ADJUSTMENT

0.25 - 20 HP

1 - 20 HP

0.1 - 3600 SEC

25 - 30 HP

25 - 60 HP

0.3 - 3600 SEC

40 - 60 HP

75 - 150 HP

1.0 - 3600 SEC

Example: If ACCEL is set to 30 seconds, and the BASE FREQUENCY is set to 60

Hz, the drive will ramp from 0 Hz to 60 Hz in 30 seconds. This is a linear function,

therefore the drive would ramp up to 30 Hz in 15 seconds, etc.
NOTE: The ability to accelerate a given load at a particular rate will be limited by the

output power capability of the drive/motor combination. The acceleration of high-

inertia and high-friction loads may be affected by the current limiting characteristics

of the drive. Refer to Parameters: 16 - CURRENT, 19 - FX BOOST, and 20 - AC

BOOST for more information.
9

DECEL

(DECELERATION TIME)

DECEL sets the deceleration rate for all speed reference sources. The DECEL

setting indicates the time to decelerate from BASE FREQUENCY to 0 Hz. As with

Parameter 8 - ACCEL, this is a linear function. If the drive is set to COAST to stop,

this parameter will have no effect when a STOP command is given. The range of

adjustment for DECEL depends on horsepower, voltage, and whether Dynamic

Braking (DB) is being used. Refer to the table below:

DECELERATION LIMITS

HORSEPOWER / VOLTAGE RATING

RANGE OF ADJUSTMENT

120 - 240 Vac

Models

(NOTE 1)

480/400 Vac

Models

590 / 480 Vac

Models

WITHOUT DB

(NOTE 2)

WITH DB

0.25 - 7.5 HP

1 - 7.5 HP

----

0.3 - 3600 SEC

0.1 - 3600 SEC

10 - 15 HP

10 - 20 HP

1 - 7.5 HP

0.5 - 3600 SEC

0.1 - 3600 SEC

20 - 30 HP

25 - 60 HP

10 - 20 HP

1.0 - 3600 SEC

0.2 - 3600 SEC

40 HP

----

----

1.0 - 3600 SEC

0.3 - 3600 SEC

----

----

25 - 60 HP

2.0 - 3600 SEC

0.2 - 3600 SEC

60 HP

75 HP

----

3.0 - 3600 SEC

0.8 - 3600 SEC

----

100 - 150 HP

----

7.0 - 3600 SEC

1.8 - 3600 SEC

NOTE 1: 120/240 Vac units have the same limits as 240/200 Vac units.

NOTE 2: The parameter value can be set below the minimum value shown, but the

value shown is the operational limit of the drive. For example, if DECEL is set for 0.1

seconds on a 10 HP, 480 Vac drive without dynamic braking, the actual deceleration

time would be 0.5 seconds.