PARAMETER MENU

PARAM.

NUMBER

PARAMETER

NAME

RANGE OF

ADJUSTMENT

FACTORY

DEFAULT

52

53

54

TB14 OUT

TB15 OUT

RELAY

NONE, RUN, FAULT, /FAULT,

LOCK, @ SPEED, ABOVE #3,

I LIMIT, AUT/MAN, FLWR PR, MIN/

MAX ALARM,

INV MIN/MAX A,

MIN ALARM, INV MIN ALARM,

MAX ALARM, INV MAX ALARM,

REVERSE, SLEEP, SPD = 0HZ

NONE

55

TB5B LOSS

FAULT, SP#4, NONE

FAULT

57

SERIAL

DISABLED, W/TIMER, W/O TIMR

DISABLE

58

ADDRESS

1 - 247

30

61

PASSWORD

0000 - 9999

0019

63

SOFTWARE

(VIEW - ONLY)

(N/A)

64

MONITOR

OFF, ON

ON

65

PROGRAM

MAINTAIN, RESET 60,

RESET 50 (NOTE 4)

RESET 60

66

HISTORY

MAINTAIN, CLEAR

MAINTAIN

70

PID MODE

OFF, NORMAL, REVERSE

OFF

74

PID FB

TB-5A, TB-5B

TB-5A

75

FB @ MIN

-32768 to 32767

0.0 %

76

FB @ MAX

-32768 to 32767

100.00 %

77

P GAIN

0.0 - 999.9 %

5.0 %

78

I GAIN

0.0 - 10.0 SEC

0.0 SEC

79

D GAIN

0.0 - 10.0 SEC

0.0 SEC

80

PID ACC

0.0 - 100.0 SEC

30.0 SEC

81

MIN ALRM

FB @ MIN - FB @ MAX

0.0 %

82

MAX ALRM

FB @ MIN - FB @ MAX

0.0 %

98

LANGUAGE

ENGLISH

99

FAULT HISTORY

(VIEW - ONLY)

(N/A)

NOTE 4:

"RST HIGH" WILL APPEAR ON UNITS SET UP FOR HIGH FREQUENCY.

NOTE!
If you are working with Software M108313 or ealier (see Parameter 63),

parameters 69 and 70 are shown here as parameters 98 and 99.