13435742_EDBM101_v24

47

If an attempt is made to decelerate a high-inertia load too quickly, the motor will

regenerate voltage back into the drive. This will cause the DC bus voltage to rise,

which can result in a HI VOLTS fault. In order to prevent faulting, the drive will enter

DECEL FREEZE, which halts the deceleration until the DC bus voltage returns to

a normal level. The drive will then begin to decelerate again, and if necessary, will

enter DECEL FREEZE repeatedly to avoid faulting. If a very short deceleration time

is programmed, DECEL FREEZE may not be able to compensate fast enough,

resulting in a HI VOLTS fault.
In applications where very short deceleration times are required on high-inertia

loads, dynamic braking may be required. Consult the factory for more information

on the Dynamic Braking option.
10

MIN FRQ

(MINIMUM FREQUENCY)

This parameter defines the lower limit of the drive’s speed range. MIN FRQ is used

in conjunction with MAX FRQ (Parameter 11 below) to define the operating range

of the drive.
If MIN FRQ is set to a value above 0.0 Hz, the drive will ramp up from 0.0 Hz when

given a start command. Once running, however, the drive will not operate below

the MIN FRQ setting unless the rotation is changed, or a stop command is issued

and the drive is programmed to ramp to a stop.
If the MINIMUM FREQUENCY is set to 0.0 Hz, the drive may be operated in ZERO

SPEED mode (drive is in RUN state, but there is no output to the motor). ZERO

SPEED operation can be used in applications requiring the ability to start and stop

the drive using only the selected speed reference. The drive will start when the

speed reference is raised above 0 VDC or 4 mA, and it will stop when the reference

is lowered to 0 VDC or 4 mA. Note that the drive must be initially started using one

of the normal start commands (keypad or terminal strip).
11

MAX FRQ

(MAXIMUM FREQUENCY)

This parameter defines the upper limit of the drive’s speed range. MAX FRQ is

used in conjunction with MIN FRQ (Parameter 10 above) to define the operating

range of the drive.

WARNING!

Consult motor manufacturer before operating motor above rated

frequency. Overspeeding the motor and/or driven equipment can cause

damage to equipment and injury to personnel!

NOTE: If the drive is equipped with the High Frequency Output option, the range of

adjustment will be 1.00 - 650.0 Hz.