1 profinet connection via the rj45 socket, 1 pin assignment, Profinet connection via the rj45 socket – Lenze E84DxxxxxxxxxR User Manual

Page 19: Communication manual 8400 protec profinet

Advertising
background image

EDS84DPNET EN 4.0 - 11/2010

L

19

Communication manual 8400 protec PROFINET

Installation

PROFINET connection

4.2.1

PROFINET connection via the RJ45 socket

A standard Ethernet patch cable is suitable for connecting the Inverter Drive 8400 protec

to a PROFINET network.



Specification of the Ethernet cable

( 20)

The installation and removal of the Ethernet cables is optimised for the use of connectors

according to the "Automation Initiative of German Domestic Automobile Manufacturers"

(AIDA).

4.2.1.1

Pin assignment

Tip!
The PROFINET interfaces feature an auto MDIX function. This function adjusts the

polarity of the RJ45 interfaces so that a connection can be established irrespective

of the polarity of the opposite PROFINET interface and irrespective of the type of

cable used (standard patch cable or crossover cable).

Note!

To prevent the RJ45 socket from being damaged, hold the Ethernet cable

connector vertically when inserting it into or unplugging it from the socket.

RJ45 socket

Pin

Signal

E94AYCXX004C

1

Tx +

2

Tx -

3

Rx +

4

-

5

-

6

Rx -

7

-

8

-

Advertising