4 error information (error), Error information (error), See the chapter – Lenze E84DxxxxxxxxxR User Manual

Page 51: Error information, Error), Communication manual 8400 protec profinet, Parameter data transfer error information (error)

Advertising
background image

EDS84DPNET EN 4.0 - 11/2010

L

51

Communication manual 8400 protec PROFINET

Parameter data transfer

Error information (error)

8.4

Error information (error)

Error code

Meaning

Description

Additional

information

0x0000

Impermissible parameter

number

Access to unavailable parameter

-

0x0001

Parameter value cannot be

changed

Change access to a parameter value that cannot be

changed

Subindex

0x0002

Lower or upper value limit

exceeded

Change access with value outside the value limits

Subindex

0x0003

Faulty subindex

Access to unavailable subindex

Subindex

0x0004

No array

Access with subindex to non-indexed parameter

-

0x0005

Incorrect data type

Change access with value that does not match the

data type of the parameter

-

0x0006

Setting not permitted (can

only be reset)

Change access with non-zero value where this is not

permitted

Subindex

0x0007

Description element cannot

be changed

Change access to a description element that cannot

be changed

Subindex

0x0008

Reserved

(PROFIdrive Profile V2: PPO-Write requested in IR is

not available)

-

0x0009

No description data available Access to unavailable description (parameter value is

available)

-

0x000A

Reserved

(PROFIdrive Profile V2: Wrong access group)

-

0x000B

No parameter change rights Change access without parameter change rights

-

0x000C

Reserved

(PROFIdrive Profile V2: Wrong password)

-

0x000D

Reserved

(PROFIdrive Profile V2: Text cannot be read in cyclic

data transfer)

-

0x000E

Reserved

(PROFIdrive Profile V2: Name cannot be read in cyclic

data transfer)

-

0x000F

No text array available

Access to unavailable text array (parameter value is

available)

-

0x0010

Reserved

(PROFIdrive Profile V2: No PPO-Write)

-

0x0011

Request cannot be executed

because of operating state

Access is not possible for temporary reasons that are

not specified in detail

-

0x0012

Reserved

(PROFIdrive Profile V2: Other error)

-

0x0013

Reserved

(PROFIdrive Profile V2: Date cannot be read in cyclic

data transfer)

-

0x0014

Impermissible value

Change access with a value that is within the value

limits but is not permissible for other permanent

reasons (parameter with defined single values)

Subindex

0x0015

Response too long

The length of the current response exceeds the

maximum transmittable length

-

0x0016

Impermissible parameter

address

Impermissible value or value which is not supported

for the attribute, number of subindexes, parameter

number, or subindex, or a combination

-

0x0017

Impermissible format

Write request: Impermissible parameter data format

or parameter data format which is not supported

-

0x0018

Number of values not

consistent

Write request: Number of parameter data values

does not match the number of subindexes in the

parameter address

-

0x0019

Reserved

-

-

...
0x0064

Advertising