EDS84DPNET EN 4.0 - 11/2010

L

25

Communication manual 8400 protec PROFINET

Commissioning

Setting the station name

5.3

Setting the station name

The station name ...

 is required for unambiguous addressing of the Inverter Drive 8400 protec by the IO

controller.

 can either be assigned by the IO controller via PROFINET or set manually in the

»Engineer«.

 has to be allocated according to the PROFINET specification:

– 1 or several labels separated by ".".
– Max. length per label: 63 characters
– Max. total length: 240 characters
– Permissible characters: [a ... z], [0 ... 9], [.], [-]
– Labels must not begin or end with [-].

 Prohibited syntax:

– "n.n.n.n" (n = 0 ... 999)
– "port-xyz" (x, y, z = 0 ... 9)
– "port-xyz-abcde" (a, b, c, d, e, x, y, z = 0 ... 9)

Note!

• The "Node blinking test" PROFINET function, which serves to identify an

accessible device, is supported. The red LED "BUS-ERR" flickers during

execution (

LED status displays

( 56)

).

• In the event of impermissible settings, the red LED "BUS-ERR" is blinking. In

this case, the Inverter Drive 8400 protec continues to work internally with the

deleted name. Operation on the PROFINET requires a valid station name.

• If the station name is assigned by the IO controller via PROFINET the change

is activated immediately. The current station name is displayed in code

C13864

.