Communication manual 8400 protec PROFINET

Commissioning

Configuring the PROFINET IO controller

24

L

EDS84DPNET EN 4.0 - 11/2010

5.2

Configuring the PROFINET IO controller

First you have to configure the IO controller for communication with the Inverter Drive

8400 protec.

Configuration for the IO controller
For configuring PROFINET, the current PROFINET device description file (XML) of the

Inverter Drive 8400 protec must be imported in the IO controller.
The current device description file GSDML-Vx.z-Lenze-8420-PNabb-yyyymmdd.xml can be

found on the Lenze Internet pages further on in the "Services & Downloads" area at:

www.Lenze.com

Definition of the user data length
The user data length is defined during the initialisation phase of the IO controller.
The Inverter Drives 8400 protec support the configuration of max. 16 process data words

(max. 32 bytes).

Description of the device data base file

Example of device data base file selection

 "PCD (8W) AR cons." = process data words (8 words)
 "Safety (4W) AR" = safety data words (4 words)

Tip!
A detailed consistency description is provided in the chapter "

Consistent

parameter data

"

( 53)

.

Wildcard in the file name "GSDML-Vx.z-Lenze-8420-PNabb-yyyymmdd.xml"
x

Main version of the GSDML scheme used

z

Subversion of the GSDML scheme used

a

Major version of the software version

Starting from this 8400 protec PROFINET version, the

device description file can be used.

bb

Minor version of the software version

yyyy

Year

mm

Month

dd

Day

Selection text

Parameter data

(with consistency)

Process data

(with consistency)

Assigned

I/O memory

PCD (nW) AR cons.

-

n words

n words

Safety (4W) AR

-

4 words

4 words

n = 1 ... 16 process data words