EDS84DPNET EN 4.0 - 11/2010

L

75

Communication manual 8400 protec PROFINET

Parameter reference

Parameters relevant for communication

C13880

C13881

C13885

Parameter | Name:

C13880 | Reaction on communication failure

Data type: UNSIGNED_8

Index: 10695

d

= 29C7

h

The action set in subcode 1 of the code is carried out when the node recognises that it is no longer in the

DATA_EXCHANGE status.

• Please also observe the notes in code

C13881

.

• A change in the monitoring response becomes immediately effective.
Selection list

0 No response
1 Error
3 Quick stop by trouble
4 Warning locked
6 Information

Subcodes

Lenze setting

Information

C13880/1

0: No response

"Watchdog/Data Exchange" monitoring

;

Read access ; Write access … CINH … PLC-STOP … No transfer … PDO_MAP_RX … PDO_MAP_TX … COM … MOT

Parameter | Name:

C13881 | Reaction time delay

Data type: UNSIGNED_16

Index: 10694

d

= 29C6

h

If the DATA_EXCHANGE status is exited, the response parameterised in

C13880

is activated after the time set here

has elapsed.

• The value = 65535 in this code deactivates monitoring.

• A change in the monitoring mode becomes immediately effective.
Setting range

(min. value | unit | max. value)

Lenze setting

0

ms

65535 0 ms

;

Read access ; Write access … CINH … PLC-STOP … No transfer … PDO_MAP_RX … PDO_MAP_TX … COM … MOT

Parameter | Name:

C13885 | Clear process data

Data type: UNSIGNED_8

Index: 10690

d

= 29C2

h

This code is used to set the process data that are to be processed by the IO device in order to maintain the internal

communication when the PROFINET has left the DATA_EXCHANGE status.
Selection list

(Lenze setting printed in bold)

Information

0 Use of most recent master PDOs

The last data sent by the IO controller are used.

1 PDOs are set to the value'0'

The contents of the process data are set to the value "0".

;

Read access ; Write access … CINH … PLC-STOP … No transfer … PDO_MAP_RX … PDO_MAP_TX … COM … MOT