3 writing parameters to the controller, Writing parameters to the controller, Communication manual 8400 protec profinet – Lenze E84DxxxxxxxxxR User Manual

Page 45

Advertising
background image

EDS84DPNET EN 4.0 - 11/2010

L

45

Communication manual 8400 protec PROFINET

Parameter data transfer

Writing parameters to the controller

8.3

Writing parameters to the controller

Request header

Parameter attribute

Index and subindex

Note!

• When a multi-parameter write request is processed, the parameter attribute,

index, subindex, and then the parameter format and parameter value are

repeated "n" times, "n" being the number of parameters requested.

• A parameter request must not exceed the max. data length of 240 bytes.

Byte 1

Byte 2

Byte 3

Byte 4

Request reference

Job identification

Axis

Number of indices

Field

Data type

Values

Request reference

U8

This value is specified by the IO controller.

Job identification

U8

0x02: Write parameter

Axis

U8

0x00 or 0x01

Number of indices

U8

0x"n" (n = number of parameters requested)

Byte 5

Byte 6

Attribute

Number of subindices

Field

Data type

Values

Attribute

U8

0x10: Value

Number of subindices

U8

0x00 or 0x01

Byte 7

Byte 8

Byte 9

Byte 10

Index

Subindex

High byte

Low byte

High byte

Low byte

Field

Data type

Values

Index

U16

0x0001 ... 0xFFFF (1 ... 65535)

Subindex

U16

0x0001 ... 0xFFFF (1 ... 65535)

Advertising