1 response after a correct read request, Response after a correct read request, Communication manual 8400 protec profinet – Lenze E84DxxxxxxxxxR User Manual

Page 41

Advertising
background image

EDS84DPNET EN 4.0 - 11/2010

L

41

Communication manual 8400 protec PROFINET

Parameter data transfer

Reading parameters from the controller

8.2.1

Response after a correct read request

Response header

Parameter format

Note!

• Responses to read requests do not contain parameter attributes and indexes/

subindexes.

• When a multi-parameter read request is transmitted, the parameter format

and the parameter value are repeated "n" times, "n" being the number of

parameters requested.

Byte 1

Byte 2

Byte 3

Byte 4

Request reference

(mirrored)

Response identifier

Axis

(mirrored)

Number of indices

Field

Data type

Values

Request reference

U8

Mirrored value of parameter request

Response identifier

U8

0x01: Parameter read

Axis

U8

0x00 or 0x01

Number of indices

U8

0x"n" (n = number of parameters requested)

Byte 5

Byte 6

Format

Number of values

Field

Data type

Values

Format

U8

0x02: Integer8

0x03: Integer16

0x04: Integer32

0x05: Unsigned8

0x06: Unsigned16

0x07: Unsigned32

0x09: Visible string

0x0A: Octet string

0x40: Zero

0x41: Byte

0x42: Word

0x43: Double word

Number of values

U8

• 0x01

• Number of requested subindices. (If there is more

than one subindex, only the parameter value is

repeated.)

• In the case of string codes, the number of characters

is entered here.