Profinet: internal error [0x01bc6011, Profinet: internal error [0x01bc6100, Profinet: internal error [0x01bc6101 – Lenze E84DxxxxxxxxxR User Manual

Page 63: Profinet: invalid parameter set [0x01bc641f, Profinet: error: lenze setting loaded [0x01bc6420, Profinet: invalid module configuration [0x01bc6430, 0x01bc6420, 0x01bc6100, 0x01bc6011, 0x01bc6101

Advertising
background image

EDS84DPNET EN 4.0 - 11/2010

L

63

Communication manual 8400 protec PROFINET

Error messages

Possible causes and remedies

PROFINET: Internal error [0x01bc6011]

PROFINET: Internal error [0x01bc6100]

PROFINET: Internal error [0x01bc6101]

PROFINET: Invalid parameter set [0x01bc641f]

PROFINET: Error: Lenze setting loaded [0x01bc6420]

PROFINET: Invalid module configuration [0x01bc6430]

Response (Lenze setting in bold)

Setting: not possible

…

None … System fault : Fault … Trouble … Quick stop by trouble … Warning locked … Warning … Information

Cause

Remedy

Device is defective.

Send device with error description to Lenze.

Response (Lenze setting in bold)

Setting: not possible

…

None … System fault : Fault … Trouble … Quick stop by trouble … Warning locked … Warning … Information

Cause

Remedy

Internal error

Send device with error description to Lenze.

Response (Lenze setting in bold)

Setting: not possible

…

None … System fault : Fault … Trouble … Quick stop by trouble … Warning locked … Warning … Information

Cause

Remedy

Internal error

Send device with error description to Lenze.

Response (Lenze setting in bold)

Setting: not possible

…

None … System fault : Fault … Trouble … Quick stop by trouble … Warning locked … Warning … Information

Cause

Remedy

Loading of an active parameter set was not possible.

Download application again (including module).

Response (Lenze setting in bold)

Setting: not possible

…

None … System fault : Fault … Trouble … Quick stop by trouble … Warning locked … Warning … Information

Cause

Remedy

Access via standard device to parameter set in the

memory module was not successful.

Download application again (including module).

Response (Lenze setting in bold)

Setting: not possible

…

None … System fault : Fault … Trouble … Quick stop by trouble … Warning locked … Warning … Information

Cause

Remedy

A module or submodule does not comply with the

configuration of the Siemens S7 engineering tool.

Check configuration.