Communication manual 8400 protec PROFINET

Parameter data transfer

Consistent parameter data

8.5

Consistent parameter data

In the PROFINET communication system, data are permanently exchanged between the

host (CPU + IO controller) and the Inverter Drive 8400 protec. The IO controller as well as

the CPU (central processing unit) of the host access a joint memory: the dual port

memory (DPM).

 The DPM allows data exchange in both directions (write/read):

It could happen that a slower IO controller writing would be overtaken by a faster CPU

reading within a cycle time without any further data organisation.
To avoid such an impermissible state, the parameter data to be transmitted must be

marked as "consistent".

Data communication with consistency
With consistency, either "reading" or "writing" is possible when the IO controller and the

CPU simultaneously access the memory:

 The IO controller transfers data only as a complete data set.
 The CPU can only access completely updated data sets.
 The IO controller cannot read or write data as long as the CPU accesses consistent data.

The result becomes clear from the example below:

1. As the IO controller can only write when the CPU does not read, the IO controller has to

wait until the data are completely read by the CPU.

2. The IO controller only writes a complete data set into the DPM.

Configuring consistent data

Central processing unit

(CPU)

Dual port memory

(DPM)

IO controller

CPU wants to read.

IO controller wants to write at the same

time.

Central processing unit

(CPU)

Dual port memory

(DPM)

IO controller

Note!

Consistency is achieved by an appropriate IO controller configuration.
Please refer to the corresponding documentation of your configuration

software.