Communication manual 8400 protec PROFINET

Error messages

Possible causes and remedies

64

L

EDS84DPNET EN 4.0 - 11/2010

PROFINET: Record parameter: Invalid read [0x01bc6501]

PROFINET: Record parameter: Invalid write [0x01bc6502]

PROFINET: Data output status bad [0x01bc6503]

PROFINET: Data_Exchange status quit [0x01bc6531]

PROFINET: Station name error [0x01bc6532]

Response (Lenze setting in bold)

Setting: not possible

…

None … System fault … Fault … Trouble … Quick stop by trouble : Warning locked … Warning … Information

Cause

Remedy

Invalid parameter read access

Check configuration.

Response (Lenze setting in bold)

Setting: not possible

…

None … System fault … Fault … Trouble … Quick stop by trouble : Warning locked … Warning … Information

Cause

Remedy

Invalid parameter write access

Check configuration.

Response (Lenze setting in bold)

Setting: not possible

…

None … System fault … Fault … Trouble … Quick stop by trouble : Warning locked … Warning … Information

Cause

Remedy

Output data invalid.

Connection to Siemens S7 has been interrupted.

Check cables and connections.

Plug in network cable at PROFINET terminal X256 or

X257.

Response (Lenze setting in bold)

Setting:

C13880/1

(; Adjustable response)

:

None … System fault ; Fault … Trouble ; Quick stop by trouble ; Warning locked … Warning ; Information

Cause

Remedy

The data exchange via PROFINET has been terminated.

• See also chapter "

Interruption of PROFINET

communication

"

( 55)

.

Check cables and connections.

Plug in network cable at PROFINET terminal X256 or

X257.

Response (Lenze setting in bold)

Setting: not possible

…

None … System fault … Fault … Trouble … Quick stop by trouble : Warning locked … Warning … Information

Cause

Remedy

A station name that is not conform to PROFINET has

been defined.

Change the station name according to the PROFINET

specification:

• 1 or several labels separated by ".".

• Max. length per label: 63 characters

• Max. total length: 240 characters

• Permissible characters: [a ... z], [0 ... 9], [.], [-]

• Labels must not begin or end with [-].

• Prohibited syntax:

–"n.n.n.n" (n = 0 ... 999)

–"port-xyz" (x, y, z = 0 ... 9)

–"port-xyz-abcde" (a, b, c, d, e, x, y, z = 0 ... 9)