Commissioning

Initial switch-on

5.5

Initial switch-on

Mounting instructions "Inverter Drives 8400 protec"
Observe the safety instructions and information on residual hazards.

Note!

Protection against uncontrolled restart
After a fault (e.g. short-term mains failure), it is sometimes undesirable or even

impermissible for the drive to restart.
In the Lenze setting of the Inverter Drives 8400 protec, the restart protection is

activated.
The restart behaviour of the controller can be set via C00142 ("Autostart

option"):
C00142 = 9 (Lenze setting)

– The controller remains inhibited (even when the fault is no longer active).
– Bit 0 (inhibit at power-on) and bit 3 (inhibit in the case of undervoltage) are

set.

– The drive starts in a controlled mode by an explicit controller enable: LOW-

HIGH edge on a digital input configured correspondingly (terminals X41,

X42, X43).

C00142 = 8 (enabled)

– In order to enable the device directly when switching it on, set bit 0 to zero.
– An uncontrolled restart of the drive is possible.