10 monitoring, Monitoring, Communication manual 8400 protec profinet – Lenze E84DxxxxxxxxxR User Manual

Page 55

Advertising
background image

EDS84DPNET EN 4.0 - 11/2010

L

55

Communication manual 8400 protec PROFINET

Monitoring

10

Monitoring

Interruption of PROFINET communication
An interruption of PROFINET communication in the DATA_EXCHANGE state, e.g. by cable

break or failure of the IO controller is recognised by the IO device.

The response to the interruption of communication is controlled via the following

settings:

1. During the initialisation of PROFINET communication the watchdog monitoring

time specified in the IO controller is transferred to the IO device.
If the IO device does not receive any valid process data in the DATA_EXCHANGE
state, the process data are treated according to the setting in

C13885

. (Like this

the data that were sent last by the IO controller can be used or set to zero.)
After the watchdog monitoring time has elapsed, the IO device changes to the

NO_DATA_EXCHANGE state (see

C13861

), and the red LED "BUS-ERR" is activated

(

LED status displays

( 56)

).

There is no reponse in the IO device.

2. To trigger a response in the IO device, you additionally have to set a Response of

the Inverter Drive 8400 protec

(

C13880

) under the Monitoring tab.

By setting a Response delay

(

C13881

) you can decelerate this response.

The response delay elapses when the DATA_EXCHANGE status is exited.
After this response delay has elapsed, the response set is executed with the error

message "

PROFINET: Data_Exchange status quit [0x01bc6531]

"

( 64)

.