0x6067 | 0x6867 - position window, 0x6068 | 0x6868 - position window time, 0x60f4 | 0x68f4 - following error actual value – Lenze i700 User Manual
Page 194: 0x60fa | 0x68fa - control effort, 0x60fc | 0x68fc - position demand internal value, 0x6067, 0x6867, 0x6068, 0x6868, 0x60f4

7
CiA402 device profile
7.6
Parameters for actuation of the position control
194
Lenze · i700 servo inverter · Reference manual · DMS 1.5 EN · 03/2014 · TD05
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
0x6067 | 0x6867 - Position window
0x6068 | 0x6868 - Position window time
0x60F4 | 0x68F4 - Following error actual value
0x60FA | 0x68FA - Control effort
0x60FC | 0x68FC - Position demand internal value
Symmetrical tolerance window around the target position for in-position recognition
• If the actual position is within this tolerance window for a longer period than for the time defined in [ms] in
object
for axis B) , the target position is considered as reached, and bit 10 ("Target position
reached") is set in the Statusword (
Setting range
(min. value | unit | max. value)
Lenze setting
0
[Pos unit]
4294967295 1000 [Pos unit]
Write access CINH OSC P RX TX
UNSIGNED_32
Time monitoring for the status message "target position reached"
0 = position in the target window is evaluated without time delay.
Setting range
(min. value | unit | max. value)
Lenze setting
0
ms
0 0 ms
Write access CINH OSC P RX TX
UNSIGNED_16
Current following error
Display area
(min. value | unit | max. value)
Initialisation
-2147483648
[Pos unit]
2147483647
Write access CINH OSC P RX TX
INTEGER_32
Target position for the position control
Display area
(min. value | unit | max. value)
Initialisation
-480000
[n unit]
480000
Write access CINH OSC P RX TX
Scaling: 480000/2
31
INTEGER_32
Interpolated set position for the position control in the internal unit
Display area
(min. value | unit | max. value)
Initialisation
-2147483648
Incr.
2147483647 0 incr.
Write access CINH OSC P RX TX
INTEGER_32