1 monitoring of the pole position identification, 2 pole position identification ppi (360˚), Monitoring of the pole position identification – Lenze i700 User Manual
Page 96: Pole position identification ppi (360°), 0x2c60, 0x3460, 5motor control & motor settings, Danger, Stop

5
Motor control & motor settings
5.10
Synchronous motor (SM): Pole position identification
96
Lenze · i700 servo inverter · Reference manual · DMS 1.5 EN · 03/2014 · TD05
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5.10.1
Monitoring of the pole position identification
If an error occurs during the pole position identification or the pulse inhibit gets active (e.g. due to
short-time undervoltage), the procedure is terminated with controller inhibit without a change in
settings.
If the motor was braked or blocked during the procedure, this will be recognised at the end of the
measurement and no change is made either (exception: "Pole position identification PLI (without
motion").
The error response can be parameterised:
0x2C60 | 0x3460 - Monitoring of pole position identification: Response
5.10.2
Pole position identification PPI (360°)
Functional description
If servo control for synchronous motor is set and if no error is pending, the current is increased to
141 % of the rated motor current along a ramp first after controller enable. The rotor thus provides
the necessary basis for further proceeding.
The commutation angle is changed (for 2 s) from 45° to 0° along a ramp. This brings the rotor
reliably into a defined position. Afterwards, the commutation angle is changed from 0° to 360°
along a ramp, passing through approximately 45° every 4 s. Thus, the motor carries out a complete
electrical revolution, resulting in a mechanical rotation of the motor shaft in positive direction
(clockwise when looking at the A-side of the motor). Within the 360° several measurements are
carried out and evaluated.
If the pole position identification is aborted, the response set here is triggered.
• If this behaviour is not wanted, deactivate the monitoring by selecting "0: No response".
Selection list
(Lenze setting printed in bold)
0 No response
1 Fault
2 Warning
Write access CINH OSC P RX TX
UNSIGNED_8
Danger!
The motor must not be braked or blocked during the pole position identification! For this
reason, this function is not permitted for hanging loads!
Stop!
Check the correct parameterisation of the followng monitoring modes before carrying
out the pole position identification to prevent the motor from being permanently
damaged in the event of an error:
•
Monitoring of the motor utilisation (I²xt)
•
Monitoring of the ultimate motor current