0x10f1 - ecat: behaviour in case of error, Configured via the, 0x10f1:2 – Lenze i700 User Manual
Page 45: Object, 0x10f1, 4device settings

Lenze · i700 servo inverter · Reference manual · DMS 1.5 EN · 03/2014 · TD05
45
4
Device settings
4.1
Behaviour in case of error
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Tip!
It is reasonable to set a value ≥"4" in
to tolerate a failed PDO and prevent two PDO
failures in a row.
The following table lists some possible settings:
From version 01.02
, an extrapolator is available in the i700 servo inverter for the motor control
which can extrapolate the setpoints for one cycle. If two PDO frames fail in a row, no extrapolation
takes place anymore. The last value is frozen.
Monitoring to EtherCAT line interruption
This monitoring mode generally checks whether there is an EtherCAT line interruption.
• If this is the case, the i700 servo inverter changes to the "Safe-Operational" status and triggers
an error (CiA402 error code 0x8181).
• This monitoring mode cannot be configured and functions with and without "Distributed Clock
mode" (DC mode).
0x10F1 - ECAT: Behaviour in case of error
Permitted PDO failures in a row
Monitoring threshold (
0
1 ... 2
1
4 ... 5
2
7 ... 8
3
10 ... 11
Response of the device in the event of an error
Sub.
Name
Lenze setting
Data type
Local Error Reaction
2: Device-specific status
UNSIGNED_32
Synchronisation: Error threshold
20
UNSIGNED_32
Subindex 1:
Internal device response
Selection list
(Lenze setting printed in bold)
Info
2 Device-specific status
An error response is carried out by the i700 servo inverter
only.
Write access CINH OSC P RX TX
UNSIGNED_32
Subindex 2:
Synchronisation: Error threshold
Setting for PDO frame failure detection
• If the internal frame failure error counter reaches the value set here, the Servo-Inverter i700 changes to the
"Safe-Operational" status and triggers an error (CiA402 error code 0x8700).
•
From version 01.04
, the PDO frame failure detection is activated in the Lenze setting "20".
Setting range
(min. value | unit | max. value)
Lenze setting
0
32 20
Write access CINH OSC P RX TX
UNSIGNED_32