0x2825 | 0x3025 - Axis: Operating mode
0x2832 | 0x3032 - Identification: Status word
This object serves to activate different commissioning test modes and procedures for the automatic parameter
identification.
Via the cross-reference in the information column, a detailed description of the respective function is provided.
Selection list
(Lenze setting printed in bold)
Info
0 CiA402 mode active
Normal operation (CiA402 operating modes active)
1 Manual test mode: Voltage/frequency
2 Manual test mode: Current/frequency
3 Manual test mode: Current pulse
4 Manual control mode
5 Pole position identification PPI (360°)
Synchronous motor (SM): Pole position identification
• PLI without motion
from version 01.03
.
6 Pole position identification PPI (min.
movement)
7 Pole position identification PPI (without
movement)
8 Identify inverter characteristic
Compensating for inverter influence on output
9 Identify motor parameters
Have motor parameters identified by the i700 servo
10 Identify Lh saturation characteristic
Asynchronous motor (ASM): Identifying the Lh
Write access CINH OSC P RX TX
UNSIGNED_8
Display of the status of an activated function for automatic parameter identification.
Display area
(min. value | unit | max. value)
Initialisation
0
65535 0
Value is bit-coded:
Info
Bit 0 Enable identification
An identification was activated via
for axis B) with a value > 4.
Bit 1 Identification in progress
The identification selected via
(or
for axis
B) is carried out (changes to 1 after the controller enable).
Bit 2 Identification complete
Identification has been completed
Bit 3 Identification failed
The identification failed or has been aborted by
controller inhibit.
Bits 4-15 Reserved
Write access CINH OSC P RX TX
UNSIGNED_16