Monitoring of the heatsink temperature
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
8.3
Monitoring of the heatsink temperature
In order to avoid impermissible heating of the device, the heatsink temperature is detected and
monitored.
0x2D84 | 0x3584 - Heatsink temperature
Subindex 5:
Device utilisation (Ixt): Warning threshold
Setting range
(min. value | unit | max. value)
Lenze setting
0
%
101 95 %
Write access CINH OSC P RX TX
UNSIGNED_16
Subindex 6:
Device utilisation (Ixt): Error threshold
Display area
(min. value | unit | max. value)
Initialisation
0
%
101 101 %
Write access CINH OSC P RX TX
UNSIGNED_16
Note!
In the temperature range 0 ... 80 °C, the heatsink temperature is measured with a
tolerance of -2 ... +4 °C. Outside this temperature range, the measuring accuracy
strongly decreases.
Sub.
Name
Lenze setting
Data type
Heatsink temperature: Actual temperature
INTEGER_16
Heatsink temperature: Warning threshold
80.0 °C
INTEGER_16
Heatsink temperature: Threshold - switch-on
fan
55.0 °C
INTEGER_16
Heatsink temperature: Threshold - switch-off
fan
45.0 °C
INTEGER_16
Subindex 1:
Heatsink temperature: Actual temperature
Display of the current heatsink temperature
Display area
(min. value | unit | max. value)
Initialisation
-3276.8
°C
3276.7
Write access CINH OSC P RX TX
Scaling: 1/10
INTEGER_16
Subindex 2:
Heatsink temperature: Warning threshold
Warning threshold for temperature monitoring
• If the heatsink temperature exceeds the threshold value set here, the device reports a warning. The warning
message is reset with a hysteresis of approx. 5 °C.
• If the heatsink temperature increases further and exceeds the non-adjustable error threshold (100 °C), the
device changes to the "Fault" device status. Further operation of the i700 servo inverter is disabled by controller
inhibit.
Setting range
(min. value | unit | max. value)
Lenze setting
50.0
°C
100.0 80.0 °C
Write access CINH OSC P RX TX
Scaling: 1/10
INTEGER_16