Quick start – Rockwell Automation 20-COMM-P Profibus Adapter User Manual

Page 13

Advertising
background image

Getting Started

1-5

This section is designed to help experienced users start using the
PROFIBUS adapter. If you are unsure about how to complete a step,
refer to the referenced chapter.

Quick Start

Step

Refer to

1

Review the safety precautions for the adapter.

Throughout
This
Manual

2

Verify that the PowerFlex drive is properly installed.

Drive User
Manual

3

Commission the adapter.
Set a unique node address using the switches on the adapter. If
desired, you can disable the switches and use parameter
settings instead.

Chapter 2

,

Installing
the Adapter

4

Install the adapter.
Verify that the PowerFlex drive is not powered. Then, connect
the adapter to the network using a PROFIBUS cable and to
the drive using the Internal Interface cable. Use the captive
screws to secure and ground the adapter to the drive.

Chapter 2

,

Installing
the Adapter

5

Apply power to the adapter.
The adapter receives power from the drive. Apply power to
the drive. The status indicators should be green. If they flash
red, there is a problem. Refer to

Chapter 7

,

Troubleshooting

.

Chapter 2

,

Installing
the Adapter

6

Configure the adapter for your application.
Set the parameters for the following features as required by
your application:

• Node address.

• I/O configuration.

• Fault actions.

Chapter 3

,

Configuring
the Adapter

7

Apply power to the PROFIBUS master and other devices
on the network.
Verify that the master and network are installed and
functioning in accordance with PROFIBUS standards, and
then apply power to them.

8

Configure the scanner to communicate with the adapter.
Use a network tool for PROFIBUS to configure the master on
the network.

Chapter 4

,

Configuring
the Profibus
Scanner

9

Create a ladder logic program.
Use a programming tool to create a ladder logic program that
enables you to do the following:

• Control the adapter and connected drive.

• Monitor or configure the drive using Explicit Messages.

Chapter 5

,

Using I/O
Messaging

Chapter 6

,

Using
Explicit
Messaging
(Parameter
Protocol)

20COMM-UM006A-EN-P.book Page 5 Friday, September 28, 2001 10:43 AM

Advertising