Using i/o messaging 5-15 – Rockwell Automation 20-COMM-P Profibus Adapter User Manual

Page 65

Advertising
background image

Using I/O Messaging

5-15

Figure 5.6 Example SLC Ladder Logic - Station 1 Program (Continued)

Station 1 Datalink B2
Datalink B2 (Pr. 303) set to Stop Mode A (Pr. 155).
N19:5 is controlled elsewhere in the user program.

0010

MOV

Move
Source

N19:5

1<
Dest

N20:5

1<

MOV

Station 1
Datalink B2
Write

Station 1 Datalink C1
Datalink C1 (Pr. 304) set to Preset Speed 1 (Pr. 101).
N19:6 is controlled elsewhere in the user program.

0011

MOV

Move
Source

N19:6

100<
Dest

N20:6

100<

MOV

Station 1
Datalink C1
Write

Station 1 Datalink C2
Datalink C2 (Pr. 305) set to Preset Speed 2 (Pr. 102).
N19:7 is controlled elsewhere in the user program.

0012

MOV

Move
Source

N19:7

200<
Dest

N20:7

200<

MOV

Station 1
Datalink C2
Write

20COMM-UM006A-EN-P.book Page 15 Friday, September 28, 2001 10:43 AM