Page 25

Advertising
background image

Configuring the Adapter

3-3

If the node address switches are set to “00”, the value of Parameter 03 -
[P-DP Addr Cfg]
determines the node address.

1. Set the value of Parameter 03 - [P-DP Addr Cfg] to a unique node

address.

Figure 3.1 PROFIBUS Node Address Screen on an LCD HIM

2. Reset the adapter. Refer to the

Resetting the Adapter

section in this

chapter.

The I/O configuration determines the type of data sent to the drive. Logic
Command/Status, Reference/Feedback, and Datalinks may be enabled or
disabled. A “1” enables the I/O. A “0” disables it.

1. Set the bits in Parameter 11 - [DPI I/O Config]:

Figure 3.2 I/O Configuration Screen on an LCD HIM

Bit 0 is the right-most bit. In

Figure 3.2

, it is highlighted and equals

“1.”

Setting the Node Address

Port 5 Device

20-COMM-P

Parameter #: 3
P-DP Addr Cfg

01

0 <> 126

Default = 01

Setting the I/O Configuration

Bit

Description

0

Logic Command/Reference (Default)

1

Datalink A

2

Datalink B

3

Datalink C

4

Datalink D

5 - 16 Not Used

Port 5 Device

20-COMM-P

Parameter #: 11
DPI I/O Config
x x x x x x x x x x x 0 0 0 0

1

Cmd/Ref

b00

20COMM-UM006A-EN-P.book Page 3 Friday, September 28, 2001 10:43 AM