Parameter protocol, Figure 6.2 – Rockwell Automation 20-COMM-P Profibus Adapter User Manual

Page 73

Advertising
background image

Using Explicit Messaging (Parameter Protocol)

6-3

Event

1. You format the required data and set up the ladder logic program to

send an Explicit Message request to the scanner module (download).

2. The scanner module transmits the Explicit Message Request to the

slave device over the PROFIBUS network.

3. The slave device transmits the Explicit Message Response back to

the master.

4. The controller retrieves the Explicit Message Response.

5. The Explicit Message is complete.

This protocol uses 4 words in the Profibus I/O area. Requests and
responses are a handshake procedure and cannot be batched, meaning
that if the master sends a request, it has to wait for the response before
sending a new request.

With this protocol you can:

• Read 8-bit, 16-bit, or 32-bit parameters from any DPI port

• Write 8-bit, 16-bit, or 32-bit parameters to any DPI port

• Read the Host Fault object

To enable this protocol set Parameter 23 - [Parameter Mode] to “Par
Prot” (default).

Figure 6.2 Parameter Message Format

Parameter Protocol

Bit

15-12

11

10-0

15-12

11

10-0

Parameter Access

Word 1 (PCA)

RC

SPM

PNU

RC

SPM

PNU

Parameter Access

Word 2 (IND)

Subindex

Subindex

Parameter Access

Word 3 (PVA)

Parameter value

(32 bit high word)

Parameter value

(32 bit high word)

Parameter Access

Word 4 (PVA)

Parameter value

(32-bit low word/8-bit & 16-bit

value)

Parameter value

(32-bit low word/8-bit & 16-bit

value)

Request

Response

20COMM-UM006A-EN-P.book Page 3 Friday, September 28, 2001 10:43 AM