Appendix B provides information about the PROFIBUS adapter
parameters.

The parameters in the adapter are numbered consecutively. However,
depending on which configuration tool you use, they may have different
numbers.

Topic

Page

About Parameter Numbers

B-1

Parameter List

B-1

About Parameter Numbers

Configuration Tool

Numbering Scheme

• DriveExplorer

• DriveExecutive

• HIM

• Explicit Messaging

The adapter parameters begin with parameter 1. For
example, Parameter 01 - [DPI Port] is parameter 1 as
indicated by this manual.

Parameter List

Parameter
No. Name and Description

Details

01

[DPI Port]
Port to which the adapter is connected. This will
usually be port 5.

Default:

0

Minimum:

0

Maximum:

7

Type:

Read Only

02

[DPI Data Rate]
Data rate used by the drive. This data rate is set in
the drive, and the adapter detects it.

Default:

0 = 125 K

Values:

0 = 125 K
1 = 500 K

Type:

Read Only

03

[P-DP Addr Cfg]
Node address to use if the Node address switches
are set to “00”.

Default:

1

Minimum:

00

Maximum

126

Type:

Read/Write

Reset Required:

Yes

04

[P-DP Addr Actual]
PROFIBUS node address actually used by the
adapter.

Default:

N/A

Minimum:

00

Maximum:

126

Type:

Read Only