Parameter protocol examples, Slc ladder example - station – Rockwell Automation 20-COMM-P Profibus Adapter User Manual

Page 76

Advertising
background image

6-6

Using Explicit Messaging (Parameter Protocol)

Parameter Protocol Examples

Read Examples

Figure 6.3 Overview Parameter Message Format (Read Request)

Bit 15-12

11

10-0

15-12

11

10-0

Parameter Access

Word 1 (PCA)

RC

SPM

PNU

RC

SPM

PNU

Parameter Access

Word 2 (IND)

Subindex

Subindex

Parameter Access

Word 3 (PVA)

Not Used

Parameter value high

(32 bit high word)

Parameter Access

Word 4 (PVA)

Not Used

Parameter value low

(32-bit low word/ or

8-bit/16-bit value)

Request

Response

Request

Response

RC
Set to “1” (‘0001’) binary to read

RC
“1” (‘0001’) Transferring 8-bit or 16-bit
parameter value
“2” (‘0010’) Transferring a 32-bit
parameter value
“7” (‘0111’) Request rejected (including fault
code)

SPM
Not used

SPM
Not used

PNU
Parameter number to read

PNU
Confirms the Parameter number (if
successful, equals the PNU from the
request)

Subindex
Selects which DPI port to talk to (“0” = DPI
Host, “5” =20-COMM-P on PowerFlex 70

Subindex
Confirms the DPI port (if successful, equals
the Subindex from the request)

Not Used

Parameter value high word
Contains a “0” if returning a value from a
16-bit parameter and the high word from a
32-bit parameter

Not Used

Parameter value low word
Contains the value from a 8-bit or 16-bit
parameter, the low word if reading from a
32-bit parameter, or the fault code (if RC =
“7”)

20COMM-UM006A-EN-P.book Page 6 Friday, September 28, 2001 10:43 AM