Port status indicator, Port status indicator -2 – Rockwell Automation 20-COMM-P Profibus Adapter User Manual

Page 88

Advertising
background image

7-2

Troubleshooting

ti

PORT Status Indicator

Status

Cause

Corrective Action

Off

The adapter is not powered
or is not connected
properly to the drive.

• Securely connect the adapter to the drive

using the ribbon cable.

• Apply power to the drive.

Flashing Red

The adapter is not
receiving a ping message
from the drive.

• Verify that cables are securely connected.

• Cycle power to the drive.

Solid
Red

The drive has refused an
I/O connection from the
adapter.

Another DPI peripheral is
using the same DPI port as
the adapter.

Important: Cycle power to the product after
making any of the following corrections.

• Verify that all DPI cables on the PowerFlex

drive are securely connected and not
damaged. Replace cables if necessary.

• Verify that the PowerFlex drive supports

Datalinks.

• Configure the adapter and PowerFlex drive

to use a Datalink that is not already being
used by another peripheral.

Orange

The adapter is connected
to a product that does not
support Allen-Bradley DPI
communications.

• Connect the adapter to a product that

supports Allen-Bradley DPI communications
(for example, PowerFlex drives).

Flashing Green

The adapter is establishing
an I/O connection to the
drive.

• No Action. This status indicator will turn solid

green or red.

Solid Green

The adapter is properly
connected and is
communicating with the
drive.

• No Action.

20COMM-UM006A-EN-P.book Page 2 Friday, September 28, 2001 10:43 AM

Advertising