2-4

Installing the Adapter

Figure 2.4 20-COMM-P DB-9 pin layout

5. Connect the PROFIBUS cable to the adapter, and secure it with the

two screws on the connector. (See

Figure 2.6

.)

Note: The screws on some connectors tie the Profibus cable ground/
shield to the metal of the socket. In some cases, Profibus will not
operate correctly without this connector.

Termination

The first and last node on the PROFIBUS network needs to be
terminated by using a PROFIBUS connector with terminating resistors.
Some connector manufacturers offer standard terminating connectors,
such as the yellow ERNI Profibus termination vertical connector (Part #
103659). Standard Profibus node connectors, such as the Phoenix
Subcon Plus M1 (Part #2761826), can be configured as a terminating
connector by adding resistors (See

Figure 2.5

.)

Figure 2.5 Phoenix Subcon Plus M1 connection for terminating resistors

Terminal

Signal

Function

Housing

Shield

1

Not connected

2

Not connected

3

B-LINE

Positive RxD/TxD, according
to RS485 specification

4

RTS

Request to send

5

GND BUS

Isolated GND from bus

6

+5V BUS

Isolated +5V from bus

7

Not connected

8

A-LINE

Negative RxD/TxD
according to RS485
specification

9

Not connected

6

3

8

5

390

220

390

B

A