Configuring the Profibus Scanner

4-17

Station 1 is configured as follows:

Note that Station 1 occupies 14 words (0-13).

30. The same steps for configuring Station 1 will be used for configuring

Station 2. Refer to previous steps (starting at step #9,

Page 4-7

) for

Configuring the SST-PFB-SLC Profibus Scanner-Station 2. (See

Figure 4.31

.)

Figure 4.31 Station 2 Network window

Station 2 is configured as follows:

Note that Station 2 occupies 14 words (14-27).

31. Use the null modem cable that came with the scanner to connect

COM1 on the PC and the CONFIG RS232 port on the scanner.

Note: The processor needs to be in program mode before
proceeding.

32. Right-click on the scanner in the network window and select

“Connect”. Then right-click again on the scanner in the network
window and select “Load Configuration”. If a minimum cycle time
attention window pops up, click OK to continue. After the
configuration has been loaded into the scanner, “Configured
Program” will be displayed in the message window. (See

Figure

4.32

.)

Module

M1/M0 Word

Ctrl/Stat & Ref Fdbk

0

Datalink A

2

Datalink B

4

Datalink C

6

Datalink D

8

Parameter Access

10

Module

M1/M0 Offset

Ctrl/Stat & Ref Fdbk

14

Datalink A

16

Datalink B

18

Datalink C

20

Datalink D

22

Parameter Access

24