About parameter numbers, How parameters are organized, Device parameters – Rockwell Automation 20-750-CNETC PowerFlex Coaxial ControlNet Option Module User Manual

Page 100

Advertising
background image

100

Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012

Appendix B

Option Module Parameters

About Parameter Numbers

Each parameter set is independently and consecutively numbered.

How Parameters Are
Organized

The

Device Parameters and Host Parameters are separately displayed in a

Numbered List

view order.

Device Parameters

Configuration Tool

Numbering Scheme

HIM
Connected Components Workbench software
DriveExplorer software
DriveExecutive software

The Device parameters and Host parameters begin with parameter
01. For example, Device Parameter 01 - [Port Number] and
Host Parameter 01 - [Net to Drv DL 01] are parameter 01 as
indicated by this manual.

Explicit Messaging

See

Chapter 6

, Using Explicit Messaging and

Appendix C

,

ControlNet Objects for details.

Parameter

No.

Name and Description

Details

01

[Port Number]
Displays the drive port into which the option module is installed.
Typically, this will be Port 4, 5, or 6.

Minimum:

4

Maximum:

6

Type:

Read Only

02

[DLs From Net Act]
Displays the number of controller-to-drive Datalinks that the
drive is using based on the I/O connection opened by the
controller.

Minimum:

0

Maximum:

16

Type:

Read Only

03

[DLs To Net Act]
Displays the number of drive-to-controller Datalinks that the
controller is using based on the I/O connection opened by the
controller.

Minimum:

0

Maximum:

16

Type:

Read Only

04

[Net Addr Src]
Displays the source from which the option module node address
is taken. This will be either the Node Address switches (see

Figure 1 on page 18

), or the value of Device Parameter 05- [Net

Addr Cfg].

Values:

0 = Switches
1 = Parameters

Type:

Read Only

05

[Net Addr Cfg]
Sets the network node address for the option module when
Device Parameter 04 - [Net Addr Src] is set to ‘1’ (Parameters).

Default:

2

Minimum:

1

Maximum:

99

Type:

Read/Write

Reset Required:

Yes

06

[Net Addr Act]
Displays the actual network node address used by the option
module.

Minimum:

1

Maximum:

99

Type:

Read Only