Controllogix controller example – Rockwell Automation 20-750-CNETC PowerFlex Coaxial ControlNet Option Module User Manual

Page 36

Advertising
background image

36

Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012

Chapter 4

Configuring the I/O

The Configure Drivers dialog box reappears with the new driver in the
Configured Drivers list.

8.

Click Close to close the Configure Drivers dialog box.

9.

Keep RSLinx software running and verify that your computer recognizes
the drive.

10.

Verify that your computer recognizes the drive.
a. From the Communications menu, choose RSWho.
b. In the menu tree, click ‘+’ next to the ControlNet driver.

ControlLogix Controller
Example

After the option module is configured, the drive and option module will be a
single node on the network. This section provides the steps needed to configure a
simple ControlNet network (see

Figure 5

). In our example, we will configure a

ControlLogix controller with 1756-CNBR (Series D) bridge to communicate
with a drive using Logic Command/Status, Reference/Feedback, and 32
Datalinks (16 to read and 16 to write) over the network.

Figure 5 - Example ControlLogix Controller ControlNet Network

Node 0

ControlLogix Controller

with 1756-CNBR Bridge

Node 1

PowerFlex 750-Series Drive

with 20-750-CNETC

ControlNet Option Module

Node 62

Computer with

ControlNet Connection

(optional redundancy)

Channel A

Channel B

ControlNet
Network