Rockwell Automation 20-750-CNETC PowerFlex Coaxial ControlNet Option Module User Manual

Page 32

Advertising
background image

32

Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012

Chapter 3

Configuring the Option Module

Restoring Option Module
Parameters to Factory
Defaults

As an alternate reset method, you can restore the option module parameters by
using a MEMORY folder menu item instead of using

Device Parameter 07 -

[Reset Module]

described in

Resetting the Option Module on page 31

. The

MEMORY folder method provides two ways to restore the option module

Device and Host parameters:

ALL—restores ALL option module

Device and Host parameters to their

factory default values.

MOST—restores MOST option module

Device and Host parameters—

except

Device Parameter 05 - [Net Addr Cfg] which is used for network

setup.

Follow these steps to restore option module

Device and Host parameters to their

factory default values.

1.

Access the Status screen, which is displayed on HIM powerup.

2.

Use the

or

key to scroll to the Port in which the option

module is installed.

3.

Press the

key to display its last-viewed folder.

4.

Use the

or

key to scroll to the MEMORY folder.

5.

Use the

or

key to select Set Defaults.

6.

Press the

(Enter) key to display the Set Defaults pop-up box.

7.

Press the

(Enter) key again to display the warning pop-up box to

reset

Device and Host parameters to their factory default values.

8.

Press the MOST

soft key to restore MOST Device and Host parameters to

factory defaults or press the ALL

soft key to restore ALL parameters. Or

press the ESC

soft key to cancel.

9.

Reset the option module using

Device Parameter 07 - [Reset Module] or

by cycling power to the drive so that the restored parameters take effect.

IMPORTANT

When performing a Set Defaults, the drive may detect a conflict and
then not allow this function to occur. If this happens, first resolve the
conflict and then repeat this Set Defaults procedure. Common reasons
for a conflict include the drive running or a controller in Run mode.

00

Stopped

0.00 Hz

AUTO

Host Drive

240V

4.2A

Rev 3.002 Ser. A

ESC

REF

TEXT

F

PAR#