Configuring and verifying key drive parameters – Rockwell Automation 20-750-CNETC PowerFlex Coaxial ControlNet Option Module User Manual

Page 21

Advertising
background image

Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012

21

Installing the Option Module

Chapter 2

Table 1 - Drive and Option Module Start-Up Status Indications

After verifying correct operation, swing down the drive HIM bezel to its closed
position and install the drive cover. For more details on status indicator
operation, see

page 90

and

page 91

.

Configuring and Verifying Key Drive Parameters

The PowerFlex 750-Series drive can be separately configured for the control and
Reference functions in various combinations. For example, you could set the
drive to have its control come from a peripheral or terminal block with the
Reference coming from the network. Or you could set the drive to have its
control come from the network with the Reference coming from another
peripheral or terminal block. Or you could set the drive to have both its control
and Reference come from the network.

Item

Name

Color

State

Description

Drive STS Indicator

STS
(Status)

Green

Flashing

Drive ready but not running, and no faults are present.

Steady

Drive running, no faults are present.

Yellow

Flashing

When running, a type 2 (non-configurable) alarm condition exists
– drive continues to run. When stopped, a start inhibit condition
exists and the drive cannot be started (see drive parameter 933 -
[Start Inhibits]).

Steady

A type 1 (user configurable) alarm condition exists, but the drive
continues to run.

Red

Flashing

A major fault has occurred. Drive will stop. Drive cannot be started
until fault condition is cleared.

Steady

A non-resettable fault has occurred.

Red/Yellow

Flashing Alternately

A minor fault has occurred. Use drive parameter 950 - [Minor Flt
Config] to enable. If not enabled, acts like a major fault. When
running, the drive continues to run. System is brought to a stop
under system control. The fault must be cleared to continue.

Yellow/Green

Flashing Alternately

When running, a type 1 alarm exists.

Green/Red

Flashing Alternately

Drive is firmware updating.

Option Module Status Indicators

PORT

Green

Flashing

Normal operation. The option module is establishing an I/O
connection to the drive. It will turn steady green or red.

Steady

Normal operation. The option module is properly connected and
communicating with the drive.

MOD

Green

Flashing

Normal operation. The option module is operating but is not
transferring I/O data to a controller.

Steady

Normal operation. The option module is operating and transferring
I/O data to a controller.


NET A
NET B

Green

Flashing

A temporary channel error has occurred or the channel is in ‘listen-
only’ mode.

Steady

Normal operation for that channel. The option module is properly
connected and communicating on the network.

Red

Flashing

The channel is not receiving network activity.

Green/Red

Flashing Alternately

There is an invalid link configuration for that channel.

Advertising